Technical characteristics of high temperature heat pumps TERRAGOR

  1. Evaporator
  2. Compressor unit
  3. Condenser unit
  4. Internal heat exchanger
  5. Ekspansion valve
  6. Drying filter

1. Evaporator

Larger heat exchanger and heat exchange surface compared to the low-temperature Terragor heat pump.

2. Compressor unit

A special heating compressor with extra refrigerant injection into the compressor head.

3. Condenser unit

Efficient transfer of thermal energy:

  • Flexible panel geometry;
  • Optimization of asymmetry of distribution channels;
  • Low flow resistance on the water side of the heat exchanger;
  • Larger heat exchanger and heat exchange surface compared to the low-temperature Terragor heat pump.

4. Internal heat exchanger

Returns the energy that would be dissipated into the environment, back to the cooling system. Protects the compressor from influx of liquid refrigerant.

5. Exspansion valve

Expansion valve reduces the refrigerant temperature and pressure to a level at which it can evaporate and enter the evaporator unit.

6. Drying filter

Drying filter is an element of the cooling system intended for eliminating water from the refrigerant in order to prevent corrosion of system elements.

Technical characteristics of high temperature heat pumps TERRAGOR

MODEL HP BW 12 HT HP BW 15 HT HP BW 17 HT
Dimensions (HxWDG) mm 815x654x580 815x654x580 815x654x580
Mass kg 139 142 147
Heating water temperature °C 62 62 62
Refrigerant / R 407 C R 407 C R 407 C
Refrigrant mass kg 2,8 3 3,3
Sound level power* dB (A) 56,8 (±1,5 dB) 56,8 (±1,5 dB) 56,8 (±1,5 dB)
Water flow - heat source m3/h 2,75 3,36 3,95
Water flow - heating m3/h 1,95 2,41 2,88
Power supply/ Fuse V /A 400/C10 400/C16 400/C16

* Measured according to standard DIN EN 3750.

MODEL HP BW 12 HT HP BW 15 HT HP BW 17 HT
Heating power / Rated power (B0/W35)** kW 11,5/2,61 14,0/3,11 16,7/3,69
COP (B0/W35)** / 4,4 4,5 4,5
Heating power / Rated power (B0/W45)** kW 11,1/3,16 13,2/3,73 15,7/4,45
COP (B0/W45)** / 3,5 3,5 3,5
Heating power / Rated power (B0/W55)** kW 10,9/3,71 12,8/4,33 15,1/5,08
COP (B0/W55)** / 2,9 3 3

** Measured at parameters brine-water B0/W35-55; according to standard EN 14511.

HP BW 17 HT - comparison of electric and heating powers at different source temperatures (brine temperature)

17 kW | heating water up to 35°C

Source temperature °C -5 0 5 25
Rated power kW 3,7 3,7 3,9 4,3
Heating power kW 14,4 16,7 19,2 29,1
COP / 3,9 4,5 5,0 6,8

17 kW | heating water up to 55°C

Source temperature °C -5 0 5 25
Rated power kW 4,9 5,1 5,3 5,9
Heating power kW 13,0 15,1 17,5 26,4
COP / 2,7 3,0 3,3 4,7